Your Power Solutions PartnerAlpha FXM 650, 1100, 2000 UPSInstallation & Operation ManualPart # 017-230-B4Effective: 07/2013member of The
017-230-B4 Rev B8Figure 2 — Contact Layout (Standard for C1 to C5, Factory Option for C6) Battery breakerThis circuit breaker provides ov
9017-230-B4 Rev BC1: The C1 contact is energized when line power is unqualified and the Alpha FXM provides backup battery power to the load(s). It
017-230-B4 Rev B10ATS (C8): When the Alpha FXM is in the Inverter mode, this normally open relay closes sending 48 Vdc (FXM 650-48, 1100, 2000) or
11017-230-B4 Rev B3. Site PlanningWARNING!Restricted Access: The Alpha FXM must be installed in a restricted area accessible only by qualied ser
017-230-B4 Rev B123.2 Communicating with the Alpha FXMThere are several ways you can communicate with the Alpha FXM UPS:1. Using the control pan
13017-230-B4 Rev B3.3 Electromagnetic Compatibility (EMC) RequirementsObserve the following EMC requirements when setting up the Alpha FXM and it
017-230-B4 Rev B144. Unpacking Alpha FXMWARNING!The Alpha FXM is heavy, up to 16 kg (35 lb). Use proper lifting techniques. The lifting and movin
15017-230-B4 Rev B5. InstallationWARNING!The Alpha FXM module MUST be correctly grounded for proper operation.The input and output lines to and f
017-230-B4 Rev B165.2 Mounting the Alpha FXMThe Alpha FXM can be placed on a shelf with no other parts needed. Any version of the FXM can be rack
17017-230-B4 Rev B5.3 Wiring the External BatteriesWARNING!The batteries must be installed by qualied personnel trained in the safe use of high-
017-230-B4 Rev B185.3.2 Wiring the Alpha FXMWARNING!Make sure the line power is off. Switch off all circuit breakers on the Alpha FXM before maki
19017-230-B4 Rev B5.3.3 Procedure1. If used, connect the following ports (see Figure 1 on page 7 for location of numbered elements):• Ethernet
017-230-B4 Rev B206. Operating the Alpha FXM6.1 Switching the Alpha FXM On and OffUnder normal operation, the Alpha FXM is always powered ON to
21017-230-B4 Rev BFigure 9 — LCD Control Panel Logo Screen6.2 Operating from the Control Panel InterfaceThe LCD control panel provides “at a gl
017-230-B4 Rev B22Logo Screen(Figure 9)System Status Menu(Table C)Control Menu(Table B)Alarm and Fault Menus (If Active)(Table P and Table Q)Event
23017-230-B4 Rev BThe CONTROL MENU (Table B) lets you control, program and adjust the Alpha FXM for connection to traffic intersection equipment or
017-230-B4 Rev B246.2.1 The LCD Control MenuThe control menu (Table B) lets you operate the Alpha FXM or program it to suit your operating condit
25017-230-B4 Rev BTable B — Control MenuLCD display Meaning DescriptionSENSE TYPE Sense TypeThis function can only be used when the Alpha FXM is
017-230-B4 Rev B266.2.2 Battery Charging OptionsCAUTION!The adjustments to the charge algorithm must be made only by qualied personnel, who unde
27017-230-B4 Rev B6.2.3 Controlling the external fan by temperature triggered dry contactThe Temperature trigger has a user configurable range of
Alpha FXM 650, 1100, 2000 UPSInstallation and Operation ManualFor technical support, contact Alpha Technologies:Canada and USA: 1-888-462-7487Internat
017-230-B4 Rev B286.2.4 Making MeasurementsThe System Status menu lets you make measurements of various Alpha FXM inputs, outputs, temperatures a
29017-230-B4 Rev B6.2.5 Viewing the 200-Event LogUse the LCD display to view up to the last 200 events, and the malfunctions that triggered each
017-230-B4 Rev B30Figure 12 — Web GUI (UPS Specification screen shown)A Screen selection menusB Current UPS operating mode. Updates automaticall
31017-230-B4 Rev BCAUTION!To successfully complete this procedure, you should have a working knowledge of network protocols and how to congure th
017-230-B4 Rev B326.3.2 UPS SpecificationsThis screen displays the Alpha FXM2000 specifications.Figure 14 — UPS Specification screen6.3.3 UPS Mo
33017-230-B4 Rev BFigure 16 — UPS Monitoring: Battery & Inverter screen—standard charging methodUPS Monitoring > Battery & InverterSh
017-230-B4 Rev B34Figure 19 — UPS Monitoring: User Input Status screenMonitoring > User Input StatusShows the current status of the user prog
35017-230-B4 Rev B6.3.4 UPS Maintenance MenusUse the UPS Maintenance screens to configure and adjust the Alpha FXM to meet your operating needs. T
017-230-B4 Rev B36Restoring All Parameters to Default ValuesThe purpose of this command is to reset the Alpha FXM to the factory default parameter
37017-230-B4 Rev BTable D — Parameters/ Default SettingsEnd minute of rush hour of time of day action period #2 00Format setting of date display
017-230-B4 Rev B2Table of Contents1. Safety ...
017-230-B4 Rev B38Figure 22 — UPS Maintenance: Battery, Standard charging methodUPS Maintenance > BatterySetting the Battery Charging Method
39017-230-B4 Rev BNOTE:The Battery Runtime Remaining algorithm attempts to calculate the health of the battery to get a more accurate prediction o
017-230-B4 Rev B40Figure 24 — UPS Maintenance: Inverter screenUPS Maintenance > InverterInverter Enabled/DisabledEnabled: the inverter can fu
41017-230-B4 Rev BFigure 25 — UPS Maintenance: Relay & Load Shed screenUPS Maintenance > Relay & Load ShedThe Alpha FXM has up to 6 d
017-230-B4 Rev B42Programmable Dry Contact Time of Day ActionYou can assign a dedicated timer to a dry contact. Upon entering the Inverter operati
43017-230-B4 Rev BYou can define up to 2 peak time periods of the day in the Maintenance > Relay & Load Shed screen:1. In the Time of Day A
017-230-B4 Rev B44Controlling the external fan with a temperature triggered dry contactThe Temperature trigger has a user configurable range of +20
45017-230-B4 Rev BUPS Maintenance > Password: used to reset the Alpha FXM password, which is limited to 4 alphanumeric characters. The factory
017-230-B4 Rev B46Figure 34 — User Input Configuration: Setting the Trigger TypeFigure 35 — User Input Configuration: Setting the Logic Level3
47017-230-B4 Rev BFigure 36 — User Input Configuration: Setting an Action6. Click the Update Configuration button and enter the password to confi
3017-230-B4 Rev B9. Specications ...
017-230-B4 Rev B48Event HistoryThis screen shows the last 200 events recorded by the Alpha FXM. Choosing a number in the Event Index drop-down box
49017-230-B4 Rev BAll EventsTo see the latest events, click Get Events and wait for the latest events to download from the FXM. It might take a co
017-230-B4 Rev B506.3.6 Upgrade FilesThis feature is available only on Alpha FXM UPS equipped with the network interface card factory option.To u
51017-230-B4 Rev BFigure 44 — Configure Site Information6.3.7 Configure Site InformationThis screen is used to enter site location information i
017-230-B4 Rev B52Email NotificationNOTE:The FXM communications module does not pass authentication details to the SMTP server. You must enable ano
53017-230-B4 Rev BFigure 47 — Test Email featureTest EmailThe Test Email feature tests the operation of the email notification option. Mail serve
017-230-B4 Rev B546.3.9 Keep AliveActivation of the Keep Alive feature provides a method to restore communications when a communication failure i
55017-230-B4 Rev BKeep Alive Method to detect communication failure:a. Ping is the only option in the Protocol field.b. In the IP Address field, e
017-230-B4 Rev B566.4 The Alpha UPS Monitor InterfaceCAUTION!Close the Alpha UPS Monitor application and disconnect when not in use.The Alpha UPS
57017-230-B4 Rev B6.4.1 Installation and Set Up of the Alpha UPS MonitorThe following tools and materials are required:• Alpha UPS Monitor, avai
017-230-B4 Rev B41. SafetySAVE THESE INSTRUCTIONS: This manual contains important safety instructions that must be followed during the installati
017-230-B4 Rev B58This screen shows the most recent events recorded by the Alpha FXM. (Once the number of events reaches 200, the oldest entries a
59017-230-B4 Rev B6.4.3 Other Alpha UPS Monitor FunctionsAlpha UPS Monitor interface is similar to the Web interface. Refer to the corresponding
017-230-B4 Rev B606.5 HyperTerminal InterfaceThe Alpha FXM front panel has a DE-9 female connector. When connected to a PC with Windows HyperTerm
61017-230-B4 Rev B6.5.2 Main Menu ScreenThe main menu screen (Figure 54) shows the Alpha FXM current input and output values, displays any faults
017-230-B4 Rev B62HyperTerminal Menu TreeSubmenus #1 and 2 are read-only screens for monitoring the Alpha FXM. To control the Alpha FXM, use sub-m
63017-230-B4 Rev B6.5.3 Line StatusLine status reports the line condition. For an updated value, press Enter.Table E — Line Status (see Figure
017-230-B4 Rev B646.5.5 Fault and Alarm DisplaysFaults and alarms display on the main menu screen. See Chapter "8. Troubleshooting" on
65017-230-B4 Rev B6.5.6 Adjusting and Controlling the Alpha FXMUse submenu #3, the Maintenance submenu (Figure 54 and Figure 55) to control the A
017-230-B4 Rev B666.5.7 Programming the Dry ContactsThe Alpha FXM front panel contacts C1 to C5 can be programmed to meet your specifications. Dry
67017-230-B4 Rev BControlling the external fan by temperature triggered dry contact The Temperature trigger has a user configurable range of +20°C
5017-230-B4 Rev B1.2 General Warnings and CautionsYou must read and understand the following warnings before installing the Alpha FXM and its com
017-230-B4 Rev B686.5.8 Setting the Date and TimeYou can adjust the Alpha FXM date and time.Table M — Setting the Date and TimeDescription Ente
69017-230-B4 Rev B6.5.9 Viewing the Serial NumberTo display the serial number of the Alpha FXM UPS, type "∗QY0" at the command line and
017-230-B4 Rev B706.5.11 200-event LogUp to 200 events are stored in the Alpha FXM log. If more than 200 events occur, the oldest is over-written
71017-230-B4 Rev BProcedure1. Type default:all and press Enter.2. Alpha FXM returns *OK as confirmation.6.5.12 Restoring All Parameters to Defau
017-230-B4 Rev B727. Maintenance7.1 Upgrading the FXM FirmwareThe Alpha FXM firmware can be reinstalled or upgraded via an RS232 interface using
73017-230-B4 Rev B6. Click on Open File to browse to the software file location (only .sx or .fbin files are supported)7. Click on Apply the updat
017-230-B4 Rev B749. The FXM will reset automatically once the upgrade is finished. Check if the LCD logo screen appears as follows:10. If upgrad
75017-230-B4 Rev B7.2 .3 Battery MaintenanceThe batteries supplied with this unit are sealed and maintenance free. Regularly ensure that all conn
017-230-B4 Rev B76WARNING!Read and understand the battery safety instructions in “Product Safety Information”.CAUTION!Make sure all the replacemen
77017-230-B4 Rev B7.3 Preventative MaintenancePerform preventative maintenance on the Alpha FXM module every 6 to 12 months. For mission critical
017-230-B4 Rev B6• Never let live battery wires touch the Alpha FXM, the enclosure or any other metal objects. This can cause a fire or explosion.
017-230-B4 Rev B788. TroubleshootingWhen the front panel alarm LED is illuminated or flashing, the Alpha FXM has a malfunction. The alarm and faul
79017-230-B4 Rev BTable Q — Fault SubmenuLCD Shows Problem Description What To DoOverload FaultThe load draws more power than the Alpha FXM can
017-230-B4 Rev B809. SpecificationsTable S — Mechanical SpecicationsParameter ValueDimensions H x W x D mm (in) FXM 1100-2000: 5.22 x 15.5 x 8
81017-230-B4 Rev BTable T — Electrical SpecicationsParameter ValueInputVoltage (nominal), Vac120 or 230, optional 208, 210, 240 for FXM 2000,
017-230-B4 Rev B82Table T — Electrical SpecicationsParameter ValueBattery Charger Current, AmpsFXM 650: 10FXM 1100/2000: 15.Battery Charger Tem
83017-230-B4 Rev B10. WarrantyAlpha Technologies Ltd warrants all equipment manufactured by it to be free from defects in parts and labor, for a
017-230-B4 Rev B84Complete the following for your records:Serial # Options Purchase Date This unit was purchased from:Deal
85017-230-B4 Rev BAppendix A - Peukert Number and Battery CapacityA.1 IntroductionThe Alpha FXM series UPS units run on batteries when the AC uti
017-230-B4 Rev B86A.4 ExampleThe following example shows how to calculate Peukert’s number and capacity from a configured battery string.Consider
87017-230-B4 Rev BA.5 Using the SpreadsheetDownload the spreadsheet “Peukert’s Parameters Calculator.xls” from www.alpha.ca website. Enter the Ba
7017-230-B4 Rev B2. General Description2.1 OverviewThe Alpha FXM is available in 3 models – FXM 650, FXM 1100 and FXM 2000. The FXM 650 and the
017-230-B4 Rev B88Appendix B - Types of TriggersThere are 3 types of trigger:B.1 Edge triggerWhen the user input changes from one state to the ot
89017-230-B4 Rev BLevel AlternativeWhen the level is set to High, the Alpha FXM is triggered to perform the next action when the user input change
Visit us at www.alpha.ca Due to continuing product development, Alpha Technologies reserves the right to change specifications without notice. Copyrig