F R O M A L P H A T E C H N O L O G I E SOperator’s ManualAlpha CFR 600, CFR 600XTand CFR 1000U N I N T E R R U P T I B L E P O W E R S U
1. INTRODUCTION4RETURN THE ENCLOSEDWARRANTY CARD TO ALPHA TECHNOLOGIESModel #Serial #OptionsPurchase dateDealer nameCityState/ProvinceZip/Postal CodeC
2. FEATURES2.1 A Tour of the CFRThe Alpha CFR is designed to be easy to use and extremely flexible.The CFR’s interchangeable front panel interface dev
2. FEATURES2.3 CFR Rear PanelAC INPUT ConnectorThe UPS is equipped with a standard, grounded AC power cord.EXTERNAL BATTERY ConnectorThe connector acc
72. FEATURESOUTPUTReceptaclesFigure 2CFR 1000 Rear PanelExhaust FanExternal I2D(MMJ)ConnectorRS-232(DE-9)ConnectorLANInterface(DE-9)ConnectorExternal
2. FEATURES8Figure 3CFR Front Panel with Standard Interface DeviceStandard Interface Device2.4 Information Management OptionsStandard Interface Device
2. FEATURES9Figure 4Intelligent Interface Device2.4 Information Management Options, continuedIntelligent Interface Device (optional)The Intelligent In
2. FEATURES102.5 Communication / Interface OptionsThe CFR is equipped with four rear panel jacks for communicationand remote interfaces: RS-232 Serial
2. FEATURES2.5 Communication / Interface Options, continued11Pin 1Pin 5Pin 6 Pin 9DE-9 Connector (RS-232 and LAN)RS-232 Serial ConnectorExternal Alarm
2. FEATURES122.5 Communication / Interface Options12 Tx3 Rx45 Gnd67 RTS *8 CTS *9RS-232 Connections with desktop I2D:With the desktop I2D the cable co
12 LINE FAIL34 COMMON5 LOW BATTERY6 OUTPUT SHUTDOWN7 GND8 +12VDC, 5mA max.92. FEATURESLAN Interface ConnectorThe Alpha UPS provides a LAN interface po
Alpha CFR 600, CFR 600XTand CFR 1000Operator’s ManualU N I N T E R R U P T I B L E P O W E R S U P P L I E S©1995 Alpha Technologies 017-100-B0
External I2D ConnectorThe external I2D connector provides an interface for the optionaldesktop Intelligent Interface Device (I2D). This allows the CF
2. FEATURES2.5 Communication / Interface Options, continued15N.C.Pin out: (RJ-45 connector, Female)1. LINE FAIL, COM contact2. LINE FAIL, N. C. cont
163. INSTALLATION3.1 Pre-InstallationDO NOT CONNECT THE UPS TO A LINE CONDITIONER, ISOLATIONTRANSFORMER OR ANY OTHER SIMILAR TYPE OF DEVICE. DAMAGETO
173. INSTALLATIONFigure 6CFR 1000 Rear PanelUPSReceptacle3.2 Connecting the CFR1. Connect the CFR's AC power cord to the wall receptacle.2. If us
The CFR is designed so that battery backup time can be greatlyextended simply by plugging the EBP 24 External Battery Pack into the backof the UPS. B
4.1 Start-up and Test1. Plug the CFR’s AC line cord into a wall receptacle. The TEST LED andOUTPUT LOAD display LEDs will flash for a few seconds to
204. OPERATION4.1 Start-up and Test, continuedSwitching OFF the UPS:1. Switch all equipment connected to the UPS OFF.2. Switch the rear panel “BATTERY
4.2 Using the Standard Interface DeviceThe Standard Interface Device displays vital UPS operating parametersand has the ability to self-test the UPS a
4.2 Using the Standard Interface Device224. OPERATIONFigure 10Test LED and Output Load LED IndicatorsUPS Powering UpWhenever the CFR is powering up, t
4. OPERATION4.2 Using the Standard Interface Device23Line SynchronizationWhen both the “LINE POWER” and “LINE FAILURE” LEDs are ON, theUPS is synchron
IMPORTANT SAFETY INSTRUCTIONSCONTAINED IN THIS MANUALCAUTIONRISK OF ELECTRICAL SHOCKCAUTION: TO REDUCE THE RISK OF ELECTRICALSHOCK, AND TO ENSURE THE
244.2 Using the Standard Interface Device, continuedLow Battery WarningThe red “LOW BATTERY WARNING” LED precedes “LOW BATTERYSHUTDOWN” by 2 to 5 minu
4.2 Using the Standard Interface Device, continuedAlarm Off SwitchThe switch cancels the audible LOW BATTERY WARNING alarm. Thealarm remains disabled
Alpha Technologies - CFRMicro Serial#00000000Opening Menu1 System Parameters2 Input Parameters3 Output Parameters4 Battery Parameters5 User Parameter
275.2 RS-232 Menu Selection IconsIcons have been placed throughout this section to easily guide you tokey commands using remote terminal emulation. T
28The menu items outlined in this manual can be accessed from a remoteterminal. The numbers contained in this guide act as a quick reference toaccess
5.4 Menu Commands OverviewOverview:The following section provide a general overview of the menu structureand give some examples of how to perform cert
5.4 Menu Commands Overview, continuedCalibrating the CFRThe CFR-UPS may be calibrated using two sets of parameters -Maintenance Parameters (commands “
5.5 System ParametersThe “SYSTEM PARAMETERS” screen provides UPS battery tempera-ture information and manual initiation and termination of SELF TEST.B
325.6 Input Parameters“INPUT PARAMETERS” provides UPS Input Voltage, Current, VoltAmps, Power in Watts, Power Factor, and Line Frequency information.V
3335.7 Output Parameters“OUTPUT PARAMETERS” provides UPS Output Voltage, Current, VoltAmps, Power in Watts, Power Factor, and Line Frequency informati
THE ALPHA CFRIMPORTANT SAFETY PRECAUTIONSCAREFULLY UNPACK THE CFR. REPORT ANY SHIPPING DAMAGE IMMEDI-ATELY.PLEASE READ THE OPERATORS MANUAL. IF YOU
3445.8 Battery Parameters“BATTERY PARAMETERS” provides UPS Battery Voltage, ChargerCurrent, and Charger Status information.VoltageVoltage indicates th
3555.9 User Parameters“USER PARAMETERS” allows you to set the information forautomatic test, output voltage shutdown, display unit identification, and
365.9 User Parameters, continued55535. RS-232 TERMINAL COMMUNICATIONSet Test ScheduleThe UPS can be setup to perform a routine self-test at intervals
37Set User Security CodeThe security code is used to restrict entry into certain areas of theprogram. The code (1111) is preset at the factory and al
38Cancel Output ShutdownThis command cancels any pending or current UPS output shutdown. Thiscommand requires the USER SECURITY CODE.Recover Output S
39510Disable Transmission of Unsolicited Alarms“509 None (xxxx)”; xxxx= “active” or blank; default is “active.”Setting this option to “active” disab
5.10 Maintenance Parameters“MAINTENANCE PARAMETERS” allow you to customize UPSdetection and warning characteristics. Normally, there should be no nee
5.10 Maintenance ParametersMax. PLL Slew RateIncreasing this value will reduce the speed at which the Phase LockedLoop (PLL) will change the output fr
5. RS-232 TERMINAL COMMUNICATION5.11 Parameter Dump Command (Function 0)Parameter Dump Command (Function 0)Function ‘0’ displays all UPS parameters in
5. RS-232 TERMINAL COMMUNICATION5.12 Event Descriptions (Alarms)43There are 6 alarm groups which upon activation will be displayed at the endof the op
iThe Alpha CFRTable of ContentsTHE ALPHA CFR 600 and CFR 1000UNINTERRUPTIBLE POWER SUPPLY1. INTRODUCTION 11.1 The Alpha CFR 11.2 The CFR Advantage 21.
445. RS-232 TERMINAL COMMUNICATION5.12 Event Descriptions (Alarms), continuedSeveral alarms can be triggered during the same event. If there is a los
455. RS-232 TERMINAL COMMUNICATION5.12 Event Descriptions, continuedBlackout (BLACKOUT) - The blackout alarm is triggered when the inputvoltage is los
465. RS-232 TERMINAL COMMUNICATION5.12 Event Descriptions, continuedInput Line Fail - Indicates that the UPS switched to backup power toprotect the eq
475. RS-232 TERMINAL COMMUNICATIONTerminal Emulation SetupIf you are using a terminal emulation software (such as PROCOMM) tocommunicate with the CFR,
6.1 CFR MaintenanceThe electronic components used in the UPS require no maintenance. Ifthe unit fails to perform a specific function, refer to the tr
6.3 Battery TestingTo determine the maximum amount of battery run time available, run thistest at least once a year. The length of the test can vary
6. MAINTENANCE50Figure 16Front Panel Removal Cover Screws(on rear panel)6.4 Removing the CFR Front Panel and CoverCAUTION: INTERNAL MAINTENANCE SHOUL
6. MAINTENANCE6.5 Internal Battery ReplacementFigure 17Internal Battery Replacement CFR 600(top view)Internal Battery Replacement (For CFR 600)IMPORTA
6. MAINTENANCE6.5 Internal Battery Replacement, continuedInternal Battery Replacement (For CFR 600XT and CFR 1000)IMPORTANT: READ THE SAFETY PRECAUTIO
6. MAINTENANCE6.5 Internal Battery Replacement, continued53Figure 19Battery Tie-down Strap Loop(side view)
Table of Contents, continued4. OPERATION, continued4.2 Using the Standard Interface Device 22UPS Powering UpOutput Shutdown PendingOutput Shutdown in
Plug in AC power cord.Reset breaker.Reset breaker.Wait for voltage tostabilize.Wait approximatelyone minute forsynchronization.Reset breaker.*Replace
55NoticeThis equipment generates, uses, and can radiate radio frequency energy if notinstalled and used in accordance with the instructions contained
6. MAINTENANCE56Figure 20Standard Interface Device (Troubleshooting)SERVICE LEDOUTPUT LOAD LED'sALARM OFF SwitchStandard Interface Device - Fault
6. MAINTENANCE57SYMPTOM CAUSE REMEDYOVERLOAD LED (ON)SERVICE LED (ON)ALARM OFF switchpressed and held:100% LED (Flashing)SERVICE LED (ON)ALARM OFF swi
6. MAINTENANCE586.8 Repair InstructionsBefore returning a unit to Alpha Technologies for repair, a ReturnMaterial Authorization (RMA) should first be
597.1 SpecificationsOutput Power (VA)Active Power (WATTS)Input Voltages @ 50 Hz (VAC)Input Current Max. (A)Input Voltages @ 60 Hz (VAC)Input Current M
607. SPECIFICATIONS7.1 Specifications, continuedCommon Specifications 600, [1000 ]Input Frequency 60 Hz or 50 Hz (± 3% Hz)Input Voltage Variation - 25
618. WARRANTYALPHA TECHNOLOGIESWARRANTYAlpha Technologies warrants its equipment to be free of manufacturing defectsin material and workmanship for a
IMPORTANTTHE UPS CONTAINS MORE THAN ONE LIVE CIRCUIT.DURING AN EMERGENCY, UTILITY POWER MAY BEDISCONNECTED AT THE SERVICE ENTRANCE OR MAINELECTRICAL P
1. INTRODUCTIONThe Alpha CFR-UPSprovides regulated, current-limited,output with excellent isolation and noise attenuation1.1 The Alpha CFRCongratulati
UNITED KINGDOMAlpha TechnologiesCartel Business EstateEdinburgh WayHarlow, Essex CM20 2DUTel: +44-1279-422110FAX: +44-21279-423355GERMANYAlpha Techno
1. INTRODUCTION21.2 The CFR AdvantageADVANCED POWER PROTECTION TECHNOLOGYPower protection devices can be judged by the type and quality ofpower they p
1. INTRODUCTION31.2 The CFR Advantage, continuedCOMMUNICATIONS AND INTELLIGENCE Alpha's interchangeable Standard Interface Device and Intelligent