Alpha-technologies Cordex Controller Ver.3.1x Manuale Utente Pagina 130

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 144
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 129
0700015-J0 Rev B
128
Table Q Inverter Parameters
Submenu Item
Default Setting Units
DC 2 : Vdc_in High Stop 62.0 V
DC 3 : Vdc_in Low Start           49.0 V
DC 3 : Vdc_in Low Transfer        42.0 V
DC 3 : Vdc_in Low Stop            42.0 V
DC 3 : Vdc_in High Start 61.0 V
DC 3 : Vdc_in High Transfer 62.0 V
DC 3 : Vdc_in High Stop 62.0 V
DC 4 : Vdc_in Low Start           49.0 V
DC 4 : Vdc_in Low Transfer        42.0 V
DC 4 : Vdc_in Low Stop            42.0 V
DC 4 : Vdc_in High Start 61.0 V
DC 4 : Vdc_in High Transfer 62.0 V
DC 4 : Vdc_in High Stop 62.0 V
DC 5 : Vdc_in Low Start           42.0 V
DC 5 : Vdc_in Low Transfer        39.0 V
DC 5 : Vdc_in Low Stop            39.0 V
DC 5 : Vdc_in High Start 61.0 V
DC 5 : Vdc_in High Transfer 62.0 V
DC 5 : Vdc_in High Stop 62.0 V
DC 6 : Vdc_in Low Start           42.0 V
DC 6 : Vdc_in Low Transfer        39.0 V
DC 6 : Vdc_in Low Stop            39.0 V
DC 6 : Vdc_in High Start 61.0 V
DC 6 : Vdc_in High Transfer 62.0 V
DC 6 : Vdc_in High Stop 62.0 V
DC 7 : Vdc_in Low Start           42.0 V
DC 7 : Vdc_in Low Transfer        39.0 V
DC 7 : Vdc_in Low Stop            39.0 V
DC 7 : Vdc_in High Start 61.0 V
DC 7 : Vdc_in High Transfer 62.0 V
DC 7 : Vdc_in High Stop 62.0 V
DC 8 : Vdc_in Low Start           42.0 V
DC 8 : Vdc_in Low Transfer        39.0 V
DC 8 : Vdc_in Low Stop            39.0 V
DC 8 : Vdc_in High Start 61.0 V
DC 8 : Vdc_in High Transfer 62.0 V
DC 8 : Vdc_in High Stop 62.0 V
AC : Fac_in Low Start             47.3 Hz
Vedere la pagina 129
1 2 ... 125 126 127 128 129 130 131 132 133 134 135 ... 143 144

Commenti su questo manuale

Nessun commento