LPE EnclosureInstallation and Operation ManualLPE EnclosureEffective: 05/2010member of The Group™
10031-302-B0-001 Rev A1.0 Introduction, continued1.2 LPESpecicationsandOptionsSpecicationsMechanical Option Part Number DescriptionDimensions B
031-302-B0-001 Rev A112.0 Installation2.1 Enclosure Installation, Wall-mountBefore installing an enclosure, the location and method of mounting must
12031-302-B0-001 Rev A2.0 Installation, continued2.2 Enclosure Installation, Steel or Concrete PoleTo mount the LPE on concrete or steel poles, two
031-302-B0-001 Rev A132.0 Installation, continued2.3 Enclosure Installation, Ground-mountNever transport the unit with installed batteries. Doing so
14031-302-B0-001 Rev AFig. 2-2, Ground-mount Positioning and Safety2.0 Installation, continued2.3 Enclosure Installation, Ground-mount, continued2.3
031-302-B0-001 Rev A152.0 Installation, continued2.3 Enclosure Installation, Ground-mount, continued2.3.2 Enclosure Grounding: Ground-mountFig. 2-3
16031-302-B0-001 Rev A2.0 Installation, continued2.3 Enclosure Installation, Ground-mount, continued2.3.3 Ground-mount InstallationLPE enclosures r
031-302-B0-001 Rev A172.0 Installation, continued2.3 Enclosure Installation, Ground-mount, continued2.3.3 Ground-mount Installation, continuedFig.
18031-302-B0-001 Rev A2.0 Installation, continued2.4 Dimensions89[391.41]15.414.38[111.13]21312.00[304.80]Optional SPI or SPI RFPole/wall mount bra
031-302-B0-001 Rev A19• Connection to utility power must be approved by the local utility before installing the power supply.• Electrical codes requir
PowerAlpha Technologies®
20031-302-B0-001 Rev A2.0 Installation, continued2.5 Connecting the Utility Power, continued2.5.1 Service PowerConnecting to utility power must be
031-302-B0-001 Rev A212.0 Installation, continued2.5 Connecting the Utility Power, continued2.5.1 Service Power, continuedThe breaker option is wir
22031-302-B0-001 Rev A2.0 Installation, continued2.5 Connecting the Utility Power, continued2.5.2 Connecting Coaxial Cable4. Insert Coaxial Termin
031-302-B0-001 Rev A236. Replace SPI cover and reinstall the screws.7. Verify switch on top of SPI is in the ON position.5. Insert coaxial terminat
24031-302-B0-001 Rev A2.0 Installation, continued2.5 Connecting the Utility Power, continued2.5.2 Connecting Coaxial Cable, continuedSPI OR SPI RF
031-302-B0-001 Rev A252.0 Installation, continued2.6 Battery InstallationThe following precautions must be observed when maintaining batteries:• Rem
26031-302-B0-001 Rev A2.0 Installation, continued2.6 Battery Installation, continuedProcedure:1. Place the batteries on the enclosure’s battery shel
031-302-B0-001 Rev A272.0 Installation, continued2.6 Battery Installation, continued2.6.1 Battery Terminal ConnectionsVarious types of batteries wit
28031-302-B0-001 Rev A2.0 Installation, continued2.7 Power Supply InstallationFor XM2-300 HP initial setup, please refer to the XM2-300 HP Quick St
031-302-B0-001 Rev A293.0 LPE Enclosure MaintenancePreventive Maintenance must be performed every three to six months. By establishing a routine main
031-302-B0-001 Rev A3031-302-B0-001, Rev. AEffective Date: May 2010Copyright© 2010Alpha Technologies, Inc. LPE Enclosure Installation and Operation Ma
Visit us at www.alpha.comAlpha Technologies Inc.3767 Alpha WayBellingham, WA 98226 United StatesTel: +1 360 647 2360Fax: +1 360 671 4936Alpha Technolo
4031-302-B0-001 Rev ASafety Notes ...
031-302-B0-001 Rev A5Safety NotesReview the drawings and illustrations contained in this manual before proceeding. If there are any questions regardin
6031-302-B0-001 Rev ABattery Maintenance GuidelinesThe battery maintenance instructions listed below are for reference only. Battery manufacturer’s in
031-302-B0-001 Rev A7Battery Safety NotesChemical HazardsAny gelled or liquid emissions from a valve-regulated lead-acid (VRLA) battery contain dilute
8031-302-B0-001 Rev AGrounding Connection NotesIn order to provide a ready, reliable source of backup power, it is necessary to connect the power supp
031-302-B0-001 Rev A91.0 Introduction1.1 LPE EnclosuresThe LPE Enclosures may be equipped with an optional AC service entrance, AC distribution and